The following article applies for the models listed below:
UPS Online: Atlas (FDC-003K, FDC-006K, FDC-010K).
UPS Online: Atlas (FDC-003K, FDC-006K, FDC-010K).
This article provides a table with the UPS Misuse after the average limit which is 1000 meters. The misuse of this UPS comes as follows: "Per every 100 meters after the limit which is 1000 meters the UPS will have a Altitude Misuse of 1% of the UPS performance."
Following this premise, here are the misuse percentage of the UPS after 1000 MTS Altitude.
Altitude (mts) | UPS Percent deviation (%) | FDC-003K (Watts) | FDC-006K (Watts) | FDC-010K (Watts) |
---|---|---|---|---|
1000 | 100% | 2400W | 4800W | 8000W |
1100 | 99% | 2376W | 4752W | 7920W |
1200 | 98% | 2352W | 4704W | 7840W |
1300 | 97% | 2328W | 4656W | 7760W |
1400 | 96% | 2304W | 4608W | 7680W |
1500 | 95% | 2280W | 4560W | 7600W |
1600 | 94% | 2256W | 4512W | 7520W |
1700 | 93% | 2232W | 4464W | 7440W |
1800 | 92% | 2208W | 4416W | 7360W |
1900 | 91% | 2184W | 4368W | 7280W |
2000 | 90% | 2160W | 4320W | 7200W |
2100 | 89% | 2136W | 4272W | 7120W |
2200 | 88% | 2112W | 4224W | 7040W |
2300 | 87% | 2088W | 4176W | 6960W |
2400 | 86% | 2064W | 4128W | 6880W |
2500 | 85% | 2040W | 4080W | 6800W |
2600 | 84% | 2016W | 4032W | 6720W |
2700 | 83% | 1992W | 3984W | 6640W |
2800 | 82% | 1968W | 3936W | 6560W |
2900 | 81% | 1944W | 3888W | 6480W |
3000 | 80% | 1920W | 3840W | 6400W |
3100 | 79% | 1896W | 3792W | 6320W |
3200 | 78% | 1872W | 3744W | 6240W |
3300 | 77% | 1848W | 3696W | 6160W |
3400 | 76% | 1824W | 3648W | 6080W |
3500 | 75% | 1800W | 3600W | 6000W |