Inicio > English > Online UPS > Elipse: Input/Output Connections

Elipse: Input/Output Connections

The following article applies for the models listed below:

UPS Online: Elipse (EL-6K, EL-10K).


 
If you don´t know is your UPS has a old label or new label check this link: Old Label vs New Label
 
 
The following is a list of several electrical connections available on this UPS.

The INPUT connection should be the same for all type of connections.

Note: The Neutral is not connected on the INPUT of the UPS, therefore the UPS delivers its own NEUTRAL for the OUTPUT using the Isolation Transformer.
 

Old Label:                                                                           New Label:

inputnew

Single mode or UPS connected by itself


 

OLD LABEL



oldlabel single mode


For 110/120 Outputs: 

For this type of connections you need to make sure to balance your load evenly, 50% on L1-N1 and 50% on L2-N2.

 
singlemodeold120


For 220/240V Outputs: 

You can take the needed output NEUTRAL from either N1 or L2 which are the jumped together.

Note: Remember to Ground your NEUTRAL on the output of the UPS. See Grounding at the end of the article.

singmodeold240


 

NEW LABEL

 

new label single mode


For 110/120 Outputs: 

For this type of connections you need to make sure to balance your load evenly, 50% on L1-N1 and 50% on N2-L2.





For 220/240V Outputs: 

You can take the needed output NEUTRAL from either N1 or N2 which are the jumped together.

Note: Remember to Ground your NEUTRAL on the output of the UPS. See Grounding at the end of the article.

 


GROUNDING


 
According to the the NFPA 70 NEC article 250.20(D) specifies that the NEUTRAL should be grounded on all Systems that delivers its own NEUTRAL such as Transformers,generators,UPS with isolating transformers and similar systems.

Following the
NFPA article, the output NEUTRAL of the UPS should be connected to the Output GROUND of the UPS. See the image for more information: